base unit SEP888 for Sepam series 80 - 24…250V - with mimic-based UMI

Catégorie : Schneider

Caractéristiques complémentaires

base unit SEP888 for Sepam series 80 24…250
V with mimic-based UMI
User machine interface type Mimic based
Output type Annunciation relay 127 V DC continuous current: 2 A breaking capacity: 0.5 A L/R < 20 ms
Annunciation relay 220 V DC continuous current: 2 A breaking capacity: 0.15 A L/R < 20 ms
Annunciation relay 24 V DC continuous current: 2 A breaking capacity: 2 A L/R < 20 ms
Annunciation relay 48 V DC continuous current: 2 A breaking capacity: 1 A L/R < 20 ms
Control relay 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 8 A resistive
making capacity < 15 A for 200 ms
Control relay 127 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 40 ms making
capacity < 15 A for 200 ms
Control relay 127 V DC continuous current: 8 A breaking capacity: 0.5 A L/R < 20 ms making
capacity < 15 A for 200 ms
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Control relay 127 V DC continuous current: 8 A breaking capacity: 0.7 A resistive making capacity:
Control relay 220 V DC continuous current: 8 A breaking capacity: 0.1 A L/R < 40 ms making
capacity < 15 A for 200 ms
Control relay 220 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 20 ms making
capacity < 15 A for 200 ms
Control relay 220 V DC continuous current: 8 A breaking capacity: 0.3 A resistive making capacity:
Control relay 24 V DC continuous current: 8 A breaking capacity: 4 A L/R < 40 ms making capacity:
Control relay 24 V DC continuous current: 8 A breaking capacity: 6 A L/R < 20 ms making capacity:
Control relay 24 V DC continuous current: 8 A breaking capacity: 8 A resistive making capacity: <
Control relay 48 V DC continuous current: 8 A breaking capacity: 1 A L/R < 40 ms making capacity:
Control relay 48 V DC continuous current: 8 A breaking capacity: 2 A L/R < 20 ms making capacity:
Control relay 48 V DC continuous current: 8 A breaking capacity: 4 A resistive making capacity: <
Annunciation relay 100...240 V AC 47.5...63 Hz continuous current: 2 A breaking capacity: 1 A cos
Control relay 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 5 A cos φ >
0.3 making capacity < 15 A for 200 ms
[Us] rated supply voltage 24/250 V DC tolerance - 20...10 % maximum consumption: < 16 W
Battery type Lithium 3.6 V size 1/2 AA
2 kV during 1 min conforming to IEC 60255 5
[Uimp] rated impulse withstand voltage 5 kV (1.2/50 µs) conforming to IEC 60255 5
Mechanical robustness Earthquakes in operation ( level 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
Earthquakes in operation ( level 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
Jolts de energized ( level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
Shocks de energized ( level: 2) : 27 Gn/11 ms conforming to IEC 60255-21-2
Shocks in operation ( level 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
Vibrations de energized ( level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
Vibrations in operation ( level 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
Vibrations in operation ( level Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6
Standards CSA C22.2 No 0.17 00
CSA C22.2 No 14 95
CSA C22.2 No 94 M91
Fire resistance 650 °C conforming to IEC 60695 2-11
Electromagnetic compatibility Fast transient bursts immunity tests conducted disturbances : IV (4kV, 2.5 kHz ) conforming to IEC
61000 4-4
Immunity to magnetic fields at network frequency immunity tests radiated disturbances : IV (30 A/m
(continuous) 300 A/m (13 s) ) conforming to IEC 61000-4-8
Immunity to radiated fields immunity tests radiated disturbances : III (10 V/m, 80 MHz...2 GHz )
conforming to IEC 61000 4-3
Disturbing field emission emission tests A conforming to EN 55022
Fast transient bursts immunity tests conducted disturbances : A and B (4kV, 2.5 kHz/2 kV, 5 kHz )
conforming to IEC 60255 22-4
Immunity to conducted RF disturbances immunity tests conducted disturbances : III (10 V )
conforming to IEC 60255 22-6
Surges immunity tests conducted disturbances : III (2 kV CM, 1 kV MD ) conforming to IEC
61000 4-5
Conducted disturbance emission emission tests A conforming to EN 55022
1 MHz damped oscillating wave immunity tests conducted disturbances (2.5 kV CM, 1 kV MD )
conforming to IEC 60255 22-1
1 MHz damped oscillating wave immunity tests conducted disturbances (2.5 kV CM, 2.5 kV MD )
100 kHz damped oscillating wave immunity tests conducted disturbances (2.5 kV CM, 1 kV MD )
conforming to IEC 61000 4-12
Conducted disturbance emission emission tests conforming to IEC 60255 25
Disturbing field emission emission tests conforming to IEC 60255 25
Electrostatic discharge immunity tests radiated disturbances (8 kV air, 4 kV contact ) conforming to
Electrostatic discharge immunity tests radiated disturbances (8 kV air, 6 kV contact ) conforming to
IEC 60255 22-2
Fast transient bursts immunity tests conducted disturbances (4kV, 2.5 kHz ) conforming to ANSI
Immunity to radiated fields immunity tests radiated disturbances (10 V/m, 80 MHz...1 GHz )
conforming to IEC 60255 22-3
Immunity to radiated fields immunity tests radiated disturbances (35 V/m, 25 MHz...1 GHz )
Voltage interruptions immunity tests conducted disturbances (100 % during 100 ms ) conforming to
IEC 60255 11
Climatic withstand Continuous exposure to damp heat (in operation) Cab : 10 days, 93 % RH, 40 °C conforming to IEC
60068 2-78
Continuous exposure to damp heat (in storage) Cab : 56 days, 93 % RH, 40 °C conforming to IEC
60068 2-78
Continuous exposure to damp heat (in storage) Db : 6 days, 95 % RH, 55 °C conforming to IEC
60068 2-30
Exposure to cold (in operation) Ad : - 25 °C conforming to IEC 60068-2-1
Exposure to cold (in storage) Ab : - 25 °C conforming to IEC 60068-2-1
Exposure to dry heat (in operation) Bd : 70 °C conforming to IEC 60068-2-2
Exposure to dry heat (in storage) Bb : 70 °C conforming to IEC 60068-2-2
Salt mist (in operation) Kb/2 : 6 days conforming to IEC 60068-2-52
Temperature variation with specified variation rate (in storage) Nb : - 25 °C to 70 °C, 5 °C/min
conforming to IEC 60068 2-14
Influence of corrosion/gaz test 2 (in operation) 21 days, 75 % RH, 25 °C, 0.5 ppm H2S, 1 ppm S02
conforming to IEC 60068 2-60
Influence of corrosion/gaz test 4 (in operation) 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm
S02, 0.2 ppm NO2, 0.01 ppm CI2 conforming to IEC 60068 2-60
RoHS (date code YYWW) Compliant  - since  1029  -  Schneider Electric declaration of conformity

Description