Génération du PDF…
Merci de patienter quelques secondes
ca9a5ec5cfeb
Fiche technique · 30 mai 2026
| I/O module MES120 | Sepam series 60, 80 - 14 |
|---|---|
| Logic input number 14 | 24...250 V, limits: 19.2...275 V DC input current: 3 mA threshold tripping voltage: 14 V enhanced |
| Output type Annunciation relay | 100...240 V AC 47.5...63 Hz continuous current: 2 A breaking capacity: 0.001 kA |
| Annunciation relay | 127 V DC continuous current: 2 A breaking capacity: 0.0005 kA L/R < 20 ms |
| Annunciation relay | 220 V DC continuous current: 2 A breaking capacity: 0.00015 kA L/R < 20 ms |
| Annunciation relay | 24 V DC continuous current: 2 A breaking capacity: 0.002 kA L/R < 20 ms |
| Annunciation relay | 250 V DC continuous current: 2 A breaking capacity: 0.0002 kA L/R < 20 ms |
| Annunciation relay | 48 V DC continuous current: 2 A breaking capacity: 0.001 kA L/R < 20 ms |
| Control relay | 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 0.005 kA cos φ |
| > 0.3 making capacity | < 15 A for 200 ms |
| Control relay | 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 0.008 kA |
| resistive making capacity | < 15 A for 200 ms |
| Control relay | 127 V DC continuous current: 8 A breaking capacity: 0.0002 kA L/R < 40 ms making |
| capacity | < 15 A for 200 ms |
| Control relay | 127 V DC continuous current: 8 A breaking capacity: 0.0005 kA L/R < 20 ms making |
| capacity | < 15 A for 200 ms |
| Control relay | 127 V DC continuous current: 8 A breaking capacity: 0.0007 kA resistive making |
| capacity | < 15 A for 200 ms |
| Control relay | 220 V DC continuous current: 8 A breaking capacity: 0.0001 kA L/R < 40 ms making |
| capacity | < 15 A for 200 ms |
| Control relay | 220 V DC continuous current: 8 A breaking capacity: 0.0002 kA L/R < 20 ms making |
| capacity | < 15 A for 200 ms |
| Control relay | 220 V DC continuous current: 8 A breaking capacity: 0.0003 kA resistive making |
| capacity | < 15 A for 200 ms |
| Control relay | 24 V DC continuous current: 8 A breaking capacity: 0.004 kA L/R < 40 ms making |
| capacity | < 15 A for 200 ms |
| Control relay | 24 V DC continuous current: 8 A breaking capacity: 0.006 kA L/R < 20 ms making |
| capacity | < 15 A for 200 ms |
| Disclaimer | This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications |
| Control relay | 24 V DC continuous current: 8 A breaking capacity: 0.008 kA resistive making |
| capacity | < 15 A for 200 ms |
| Control relay | 250 V DC continuous current: 8 A breaking capacity: 0.0002 kA resistive making |
| capacity | < 15 A for 200 ms |
| Control relay | 48 V DC continuous current: 8 A breaking capacity: 0.001 kA L/R < 40 ms making |
| capacity | < 15 A for 200 ms |
| Control relay | 48 V DC continuous current: 8 A breaking capacity: 0.002 kA L/R < 20 ms making |
| capacity | < 15 A for 200 ms |
| Control relay | 48 V DC continuous current: 8 A breaking capacity: 0.004 kA resistive making |
| capacity | < 15 A for 200 ms |
| Mechanical robustness Earthquakes in operation ( level | 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3 |
| Earthquakes in operation ( level | 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3 |
| Jolts de | energized ( level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2 |
| Shocks de | energized ( level: 2) : 27 Gn/11 ms conforming to IEC 60255-21-2 |
| Shocks in operation ( level | 2) : 10 Gn/11 ms conforming to IEC 60255-21-2 |
| Vibrations de | energized ( level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1 |
| Vibrations in operation ( level | 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1 |
| Vibrations in operation ( level | Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6 |
| Auxiliary connection terminal Screw | type connectors 1 cable(s) 1.5 mm² |
| Screw | type connectors 1 cable(s) 2.5 mm² |
| Screw | type connectors 2 cable(s) 1 mm² |
| Screw | type connectors 1 cable(s) 0.2...2.5 mm² |
| Screw | type connectors 2 cable(s) 0.2...1 mm² |
| Electromagnetic compatibility 1 MHz damped oscillating wave immunity tests | conducted disturbances (2.5 kV CM, 1 kV DM ) |
| conforming to IEC 60255 | 22-1 |
| 1 MHz damped oscillating wave immunity tests | conducted disturbances (2.5 kV CM, 2.5 kV DM ) |
| 100 kHz damped oscillating wave immunity tests | conducted disturbances (2.5 kV CM, 1 kV DM ) |
| conforming to IEC 61000 | 4-12 |
| Conducted disturbance emission emission tests conforming to IEC 60255 | 25 |
| Conducted disturbance emission emission tests | A conforming to EN 55022 |
| Disturbing field emission emission tests conforming to IEC 60255 | 25 |
| Disturbing field emission emission tests | A conforming to EN 55022 |
| Electrostatic discharge immunity tests | radiated disturbances (8 kV air, 4 kV contact ) conforming to |
| Electrostatic discharge immunity tests | radiated disturbances (8 kV air, 6 kV contact ) conforming to |
| IEC 60255 | 22-2 |
| Fast transient bursts immunity tests | conducted disturbances (4kV, 2.5 kHz ) conforming to ANSI |
| Fast transient bursts immunity tests | conducted disturbances: A and B (4kV, 2.5 kHz/2 kV, 5 kHz ) |
| conforming to IEC 60255 | 22-4 |
| Fast transient bursts immunity tests | conducted disturbances: IV (4kV, 2.5 kHz ) conforming to IEC |
| 61000 | 4-4 |
| Immunity to conducted RF disturbances immunity tests | conducted disturbances: III (10 V ) |
| conforming to IEC 60255 | 22-6 |
| Immunity to magnetic fields at network frequency immunity tests | radiated disturbances: IV (30 A/m |
| (continuous) | 300 A/m (1-3 s) ) conforming to IEC 61000-4-8 |
| Immunity to radiated fields immunity tests | radiated disturbances (10 V/m, 80 MHz...1 GHz ) |
| conforming to IEC 60255 | 22-3 |
| Immunity to radiated fields immunity tests | radiated disturbances (35 V/m, 25 MHz...1 GHz ) |
| Immunity to radiated fields immunity tests | radiated disturbances: III (10 V/m, 80 MHz...2 GHz ) |
| conforming to IEC 61000 | 4-3 |
| Surges immunity tests | conducted disturbances: III (2 kV CM, 1 kV DM ) conforming to IEC 61000-4-5 |
| Voltage interruptions immunity tests | conducted disturbances (100 % during 100 ms ) conforming to |
| IEC 60255 | 11 |
| Climatic withstand Exposure to cold (in operation) | Ad: - 25 °C conforming to IEC 60068-2-1 |
| Exposure to dry heat (in operation) | Bd: 70 °C conforming to IEC 60068-2-2 |
| Continuous exposure to damp heat (in operation) | Cab: 10 days, 93 % RH, 40 °C conforming to IEC |
| 60068 | 2-78 |
| Salt mist (in operation) | Kb/2: 6 days conforming to IEC 60068-2-52 |
| Influence of corrosion/gaz test 2 (in operation) | 21 days, 75 % RH, 25 °C, 0.5 ppm H2S, 1 ppm S02 |
| conforming to IEC 60068 | 2-60 |
| Influence of corrosion/gaz test 4 (in operation) | 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm |
| S02, 0.2 ppm NO2, 0.01 ppm CI2 conforming to IEC 60068 | 2-60 |
| Temperature variation with specified variation rate (in storage) | Nb: - 25 °C to 70 °C, 5 °C/min |
| conforming to IEC 60068 | 2-14 |
| Exposure to cold (in storage) | Ab: - 25 °C conforming to IEC 60068-2-1 |
| Exposure to dry heat (in storage) | Bb: 70 °C conforming to IEC 60068-2-2 |
| Continuous exposure to damp heat (in storage) | Cab: 56 days, 93 % RH, 40 °C conforming to IEC |
| 60068 | 2-78 |
| Continuous exposure to damp heat (in storage) | Db: 6 days, 95 % RH, 55 °C conforming to IEC |
| 60068 | 2-30 |
| RoHS (date code | YYWW) Compliant - since 0934 - Schneider Electric declaration of conformity |
Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 30 mai 2026. Source : https://seniadz.net/index.php/produit/59715/