Génération du PDF…

Merci de patienter quelques secondes

Fiche technique — 9f01fcb740aa — A9F73603

A9F73603

9f01fcb740aa

Fiche technique · 24 mai 2026

A9F73603

A9F73603

9f01fcb740aa

En stock

ACTI9 IC60N 1P-N 3A B DISJONCTEUR MINIAT

Catégorie : Disjoncteurs modulaires sur rail MCB: Acti9 IC60, DPN, Domae, NG125, C120

Caractéristiques complémentaires

iC60N miniature circuit breaker - 1P + N - 3A - B
Product or component type Miniature circuit breaker
Trip unit technology Thermal magnetic
Breaking capacity 50 kA Icu conforming to IEC 60947 2 - 100...133 V AC 50/60 Hz
50 kA Icu conforming to EN 60947 2 - 100...133 V AC 50/60 Hz
50 kA Icu conforming to IEC 60947 2 - 220...240 V AC 50/60 Hz
6000 A Icn conforming to EN 60898 1 - 230 V AC 50/60 Hz
50 kA Icu conforming to EN 60947 2 - 12...60 V AC 50/60 Hz
50 kA Icu conforming to EN 60947 2 - 220...240 V AC 50/60 Hz
50 kA Icu conforming to IEC 60947 2 - 12...60 V AC 50/60 Hz
6000 A Icn conforming to IEC 60898 1 - 230 V AC 50/60 Hz
Utilisation category Category A conforming to EN 60947 2
Category A conforming to IEC 60947 2
Suitability for isolation Yes conforming to EN 60947 2
Yes conforming to IEC 60947 2
Yes conforming to EN 60898 1
Yes conforming to IEC 60898 1
Standards EN 60898 1
EN 60947 2
IEC 60898 1
IEC 60947 2
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Magnetic tripping limit 4 x In +/ 20 %
[Ics] rated service breaking capacity 6000 A 100 % x Icu conforming to IEC 60898 1 - 230 V AC 50/60 Hz
6000 A 100 % x Icu conforming to EN 60898 1 - 230 V AC 50/60 Hz
50 kA 100 % x Icu conforming to EN 60947 2 - 12...60 V AC 50/60 Hz
50 kA 100 % x Icu conforming to EN 60947 2 - 220...240 V AC 50/60 Hz
50 kA 100 % x Icu conforming to IEC 60947 2 - 12...60 V AC 50/60 Hz
50 kA 100 % x Icu conforming to IEC 60947 2 - 220...240 V AC 50/60 Hz
50 kA 100 % x Icu conforming to IEC 60947 2 - 100...133 V AC 50/60 Hz
50 kA 100 % x Icu conforming to EN 60947 2 - 100...133 V AC 50/60 Hz
Limitation class 3 conforming to EN 60898 1
3 conforming to IEC 60898 1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60947 2
500 V AC 50/60 Hz conforming to EN 60947 2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947 2
6 kV conforming to IEC 60947 2
Connections terminals Single terminal, top or bottom rigid wire(s) 1...25 mm² max
Earth leakage protection Separate block
Pollution degree 3 conforming to EN 60947 2
3 conforming to IEC 60947 2
Tropicalisation 2 conforming to IEC 60068 1
Ambient air temperature for operation 35...70 °C
Ambient air temperature for storage 40...85 °C
RoHS (date code YYWW) Compliant  - since  1001  -  Schneider Electric declaration of conformity

Description

Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 24 mai 2026. Source : https://seniadz.net/index.php/produit/a9f73603/