ACTI9 IC60H 3P 2A B DISJONCTEUR MINIATUR

Catégorie : Disjoncteurs modulaires sur rail MCB: Acti9 IC60, DPN, Domae, NG125, C120

Caractéristiques complémentaires

iC60H miniature circuit breaker - 3P - 2A - B
Product or component type Miniature circuit breaker
Trip unit technology Thermal magnetic
Breaking capacity 70 kA Icu conforming to IEC 60947 2 - 12...133 V AC 50/60 Hz
70 kA Icu conforming to EN 60947 2 - 12...133 V AC 50/60 Hz
15 kA Icu conforming to EN 60947 2 - 125...180 V DC
15 kA Icu conforming to IEC 60947 2 - 125...180 V DC
70 kA Icu conforming to IEC 60947 2 - 220...240 V AC 50/60 Hz
10000 A Icn conforming to EN 60898 1 - 400 V AC 50/60 Hz
10000 A Icn conforming to IEC 60898 1 - 400 V AC 50/60 Hz
70 kA Icu conforming to EN 60947 2 - 220...240 V AC 50/60 Hz
70 kA Icu conforming to EN 60947 2 - 380...415 V AC 50/60 Hz
70 kA Icu conforming to EN 60947 2 - 440 V AC 50/60 Hz
70 kA Icu conforming to IEC 60947 2 - 380...415 V AC 50/60 Hz
70 kA Icu conforming to IEC 60947 2 - 440 V AC 50/60 Hz
Utilisation category Category A conforming to EN 60947 2
Category A conforming to IEC 60947 2
Suitability for isolation Yes conforming to EN 60947 2
Yes conforming to IEC 60947 2
Yes conforming to EN 60898 1
Yes conforming to IEC 60898 1
Standards EN 60898 1
EN 60947 2
IEC 60898 1
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
IEC 60947 2
Magnetic tripping limit 4 x In +/ 20 %
[Ics] rated service breaking capacity 7500 A 75 % x Icu conforming to EN 60898 1 - 400 V AC 50/60 Hz
7500 A 75 % x Icu conforming to IEC 60898 1 - 400 V AC 50/60 Hz
15 kA 100 % x Icu conforming to IEC 60947 2 - 125...180 V DC
15 kA 100 % x Icu conforming to EN 60947 2 - 125...180 V DC
70 kA 100 % x Icu conforming to IEC 60947 2 - 12...133 V AC 50/60 Hz
70 kA 100 % x Icu conforming to EN 60947 2 - 12...133 V AC 50/60 Hz
70 kA 100 % x Icu conforming to EN 60947 2 - 220...240 V AC 50/60 Hz
70 kA 100 % x Icu conforming to IEC 60947 2 - 220...240 V AC 50/60 Hz
70 kA 100 % x Icu conforming to EN 60947 2 - 380...415 V AC 50/60 Hz
70 kA 100 % x Icu conforming to IEC 60947 2 - 380...415 V AC 50/60 Hz
70 kA 100 % x Icu conforming to EN 60947 2 - 440 V AC 50/60 Hz
70 kA 100 % x Icu conforming to IEC 60947 2 - 440 V AC 50/60 Hz
Limitation class 3 conforming to EN 60898 1
3 conforming to IEC 60898 1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60947 2
500 V AC 50/60 Hz conforming to EN 60947 2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947 2
6 kV conforming to IEC 60947 2
Connections terminals Single terminal, top or bottom rigid wire(s) 1...25 mm² max
Earth leakage protection Separate block
Pollution degree 3 conforming to EN 60947 2
3 conforming to IEC 60947 2
Tropicalisation 2 conforming to IEC 60068 1
Ambient air temperature for operation 35...70 °C
Ambient air temperature for storage 40...85 °C
RoHS (date code YYWW) Compliant  - since  1001  -  Schneider Electric declaration of conformity

Description