C120H 1P 80A D 15000A 240/415V DISJONCTE

Catégorie : Disjoncteurs modulaires sur rail MCB: Acti9 IC60, DPN, Domae, NG125, C120

Caractéristiques complémentaires

C120H circuit breaker - 1P - 80A - D curve
Product or component type Miniature circuit breaker
Trip unit technology Thermal magnetic
Breaking capacity 30 kA Icu conforming to EN/IEC 60947 2 - 130 V AC 50/60 Hz
20 kA Icu conforming to EN/IEC 60947 2 - 12 V DC
20 kA Icu conforming to EN/IEC 60947 2 - 125 V DC
15 kA Icu conforming to EN/IEC 60947 2 - <= 144 V DC
15 kA Icu conforming to EN/IEC 60947 2 - 220...240 V AC 50/60 Hz
15000 A Icn conforming to EN/IEC 60898 1 - 230...400 V AC 50/60 Hz
4.5 kA Icu conforming to EN/IEC 60947 2 - 380...415 V AC 50/60 Hz IT
30 kA Icu conforming to EN/IEC 60947 2 - 12 V AC 50/60 Hz
Suitability for isolation Yes conforming to IEC 60947 2
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
[Ics] rated service breaking capacity 15 kA at 50 % of breaking cap. conforming to EN/IEC 60947 2 - 130 V AC 50/60 Hz
7.5 kA at 50 % of breaking cap. conforming to EN/IEC 60947 2 - 220...240 V AC 50/60 Hz
2.25 kA at 50 % of breaking cap. conforming to EN/IEC 60947 2 - 380...415 V AC 50/60 Hz
20 kA at 100 % of breaking cap. conforming to EN/IEC 60947 2 - 12 V DC
15 kA at 50 % of breaking cap. conforming to EN/IEC 60947 2 - 12 V AC 50/60 Hz
7500 A at 50 % of breaking cap. conforming to EN/IEC 60898 1 - 230...400 V AC 50/60 Hz
15 kA at 100 % of breaking cap. conforming to EN/IEC 60947 2 - <= 144 V DC
20 kA at 100 % of breaking cap. conforming to EN/IEC 60947 2 - 125 V DC
Limitation class 3 conforming to EN/IEC 60947 2
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN/IEC 60947 2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947 2
Mounting mode Clip on
Electrical durability 5000 cycles conforming to IEC 60947 2
Earth leakage protection Without
Standards EN/IEC 60947 2
EN/IEC 60898 1
Pollution degree 3 conforming to IEC 60947 2
Tropicalisation 2 conforming to IEC 60068 1
Ambient air temperature for operation 30...60 °C
Ambient air temperature for storage 40...70 °C
RoHS (date code YYWW) Compliant  - since  0627  -  Schneider Electric declaration of conformity