Génération du PDF…

Merci de patienter quelques secondes

Fiche technique — 5e6b2c7fd0ab — ABR1E118B

ABR1E118B

5e6b2c7fd0ab

Fiche technique · 17 mai 2026

ABR1E118B

ABR1E118B

5e6b2c7fd0ab

En stock

INTERF R EM E1F 24V LED

Catégorie : Contrôle, Relais et Signalisation

Caractéristiques complémentaires

input interface module 17.5 mm - electromechanical
- 24 V AC/DC 1 NO
[Ith] conventional free air thermal 2 A conforming to IEC 60947 1
Control circuit voltage limits 30 V energization threshold 16.5 V
Connections terminals Screw clamp terminal
Drop out voltage <= 3.8 V Holding current >= 4.9 mA DC
[Ue] rated operational voltage <= 125 V DC conforming to IEC 60947 5-1
<= 230 V AC conforming to IEC 60947 5-1
[Ie] rated operational current 1 A AC 13 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1
1 A AC 14 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1
1 A AC 15 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1
1 A DC 13 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-1
2 A AC 12 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1
2 A DC 12 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-1
Operating time <= 12 ms between de energisation of coil and closing of NC contact
<= 12 ms between de energisation of coil and closing of NO contact
Operating rate in Hz <= 6 Hz at no load
[Ui] rated insulation voltage 250 V conforming to IEC 60947 1
Installation category II conforming to IEC 60947 1
standards IEC 60947 5-1
fire resistance 850 °C conforming to IEC 60695 2-1
shock resistance 50 gn for 11 ms conforming to IEC 60068 2-27
vibration resistance 6 gn (f = 10...55 Hz) conforming to IEC 60068 2-6
electromagnetic compatibility 1.2/50 ms shock waves immunity test, 0.25 kV for U > 50 V conforming to IEC 255 4
1.2/50 ms shock waves immunity test, 0.5 kV for U < 50 V conforming to IEC 255 4
Electrostatic discharge immunity test level 3, 8 kV conforming to IEC 61000 4-2
Rapid transients immunity test, on input/output 1 kV conforming to IEC 61000 4-4
Rapid transients immunity test, on power supply 2 kV conforming to IEC 61000 4-4
ambient air temperature for operation 20...60 °C at Un
ambient air temperature for storage 40...70 °C
pollution degree 3 conforming to IEC 60947 5-1
(1) 2 wire sensors
(3) 3 wire sensors

Description

Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 17 mai 2026. Source : https://seniadz.net/index.php/produit/abr1e118b/