Génération du PDF…
Merci de patienter quelques secondes
b04bc005177a
Fiche technique · 7 juin 2026
| input interface module | 9.5 mm - electromechanical - 24 V DC - 1 C/O low-level |
|---|---|
| Range of product | Interface for discrete signals |
| Product or component type | Slim electromechanical input interface module |
| Product specific application | For very low level switching |
| Contacts type and composition | 1 C/O |
| [Uc] control circuit voltage | 24 V |
| Control circuit type | DC |
| Width pitch dimension | 17.5 mm |
| [In] rated current | ≤ 0.023 A |
| Reverse polarity protection | Internal for control circuit |
| Short circuit protection | 0.4 A external fuse fast blow |
| [Ith] conventional free air thermal current | 0.05 A conforming to IEC 60947-1 |
| Local signalling | 1 LED indicating control signal state |
| Control circuit voltage limits | 28.8 V |
| Connections | terminals: Screw clamp terminal |
| Operating threshold | 16.9 V |
| Drop | out voltage: ≤ 3.8 V |
| Holding current | 2 mA |
| Power dissipation in W | 0.55 W |
| Maximum switching voltage | 60 V AC, 60 V DC |
| [Ue] rated operational voltage | ≤ 48 V AC (IEC 60947-5-1), ≤ 48 V DC (IEC 60947-5-1) |
| Network frequency | 50/60 Hz |
| Minimum switching current | 0.01 mA |
| Minimum switching voltage | 0.01 V |
| Electrical reliability | 1e-008 |
| Between de | energisation of coil and closing of NC contact: ≤ 6 ms |
| Between energisation of coil and closing of NO contact DC | ≤ 6 ms |
| Contact bounce time | ≤ 2 ms |
| Non | overlap time: 2 ms on de-energisation, 5 ms on energisation |
| Operating rate in Hz | 10 Hz at no-load |
| Mechanical durability | ≥ 20000000 cycles |
| [Ui] rated insulation voltage | 250 V (VDE 0110 group C), 300 V (IEC 60947-1) |
| Flame retardance | V0 (UL 94) |
| Cable cross section | 0.27...4 mm² rigid, 0.34...2.5 mm² flexible |
| Operating position | Any position |
| Installation category | II (IEC 60947-1) |
| Mounting support | Asymmetrical/Symmetrical DIN rail |
| Product weight | 0.048 kg |
| Immunity to microbreaks | 1 ms |
| Dielectric strength | 1000 V (open contacts), 1500 V (coil-contact), 2500 V (wired interface-earth) |
| Standards | IEC 60947-5-1 |
| Product certifications | BV, CSA, DNV, LROS (Lloyds register of shipping), UL |
| IP degree of protection | IP20 (IEC 60529) |
| Protective treatment | TC |
| Fire resistance | 960 °C (IEC 60695-2-1) |
| Shock resistance | 30 gn for 11 ms (IEC 60068-2-27) |
| Vibration resistance | 3 gn (10...150 Hz) (IEC 60068-2-6) |
| 1.2/50 µs shock waves immunity | 0.5 kV for U < 50 V, 1.5 kV for U < 150 V, 2.5 kV for U < 300 V (IEC 947-1) |
| Electromagnetic field immunity | 10 V/m (27...1000 MHz) (IEC 61000-4-3) |
| Electrostatic discharge immunity | 8 kV (IEC 61000-4-2) |
| Rapid transients immunity | 1 kV (input/output), 2 kV (power supply) (IEC 61000-4-4) |
| Ambient air temperature for operation | -5...40 °C unrestricted operation, -25...70 °C at Us |
| Ambient air temperature for storage | -40...80 °C |
| Operating altitude | ≤ 3000 m |
| Pollution degree | 2 (IEC 60947-1) |
| Warranty period | 18 months |
Doté d'une tension nominale de commande de 24V CC, il convient parfaitement aux applications industrielles modernes. Sa sortie à contact unique offre une capacité de commutation de 6A sous 250V CA, répondant aux exigences des systèmes automatisés.
Certifié CE et conforme aux normes IEC 61810-1 et IEC 61810-7, il assure une fiabilité optimale. Son montage sur rail DIN facilite l'installation dans les armoires de commande.
La LED intégrée permet une visualisation rapide de l'état du relais. Avec un temps de fermeture de 10ms et d'ouverture de 5ms, le ABR2EB312B répond aux exigences des applications nécessitant une commutation rapide des signaux.
Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 7 juin 2026. Source : https://seniadz.net/index.php/produit/abr2eb312b/