Génération du PDF…
Merci de patienter quelques secondes
69e27f8dd984
Fiche technique · 8 juin 2026
| output interface module | 9.5 mm - |
|---|---|
| electromechanical | 24 V DC - 1 NC |
| [Ith] conventional free air thermal 5 A conforming to IEC 60947 | 1 |
| Control circuit voltage limits 28.8 V energization threshold | 16.9 V |
| Connections | terminals Screw clamp terminal |
| Drop | out voltage <= 3.8 V |
| [Ue] rated operational voltage <= 120 V DC conforming to IEC 60947 | 5-1 |
| <= 230 V AC conforming to IEC 60947 | 5-1 |
| [Ie] rated operational current 1 A AC | 14 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1 |
| 1 A AC | 15 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1 |
| 3 A AC | 12 Ue: 230 V per 1000000 cycles conforming to IEC 60947-5-1 |
| 1.5 A DC | 13 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-1 |
| Disclaimer | This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications |
| 1.7 A DC | 12 Ue: 24 V per 1000000 cycles conforming to IEC 60947-5-1 |
| <= 12 ms between de | energisation of coil and closing of NO contact DC |
| Contact bounce time <= 5 ms Operating rate in Hz 10 Hz at no | load 0.5 Hz at Ie Mechanical durability >= 10000000 cycles |
| 300 V conforming to IEC 60947 | 1 |
| Installation category II conforming to IEC 60947 | 1 |
| Standards IEC 60947 | 5-1 |
| Fire resistance 960 °C conforming to IEC 60695 | 2-1 |
| Shock resistance 30 gn for 11 ms conforming to IEC 60068 | 2-27 |
| Vibration resistance 3 gn (f = 10...150 Hz) conforming to IEC 60068 | 2-6 |
| Electromagnetic compatibility 1.2/50 µs shock waves immunity test, 0.5 kV for U < 50 V conforming to IEC 60947 | 1 |
| 1.2/50 µs shock waves immunity test, 1.5 kV for U < 150 V conforming to IEC 60947 | 1 |
| 1.2/50 µs shock waves immunity test, 2.5 kV for U < 300 V conforming to IEC 60947 | 1 |
| 61000 | 4-3 |
| Electrostatic discharge immunity test level 3, 8 kV conforming to IEC 61000 | 4-2 |
| Fast transients immunity test level 3, on input/output 1 kV conforming to IEC 61000 | 4-4 |
| Fast transients immunity test level 3, on power supply 2 kV conforming to IEC 61000 | 4-4 |
| Ambient air temperature for operation | 5...40 °C unrestricted operation |
| Ambient air temperature for storage | 40...80 °C |
| Operating altitude <= 3000 m Pollution degree 2 conforming to IEC 60947 | 1 Contractual warranty Warranty period 18 months 2 Product data sheet ABR2S112B Dimensions Drawings Slim Electromechanical Interface Module Dimensions 3 Product data sheet ABR2S112B Connections and Schema Slim Electromechanical Interface Module Example of Application with PLC Interfacing PLC discrete outputs (1) Essential on inductive loads (can be replaced with peak limiter) (2) PLC positive logic transistor (or relay) outputs (3) PLC analog inputs (4) Channel X (5) Analog sensors 4 Product data sheet ABR2S112B Connections and Schema Slim Electromechanical Interface Module Circuit Diagram 1 N/O 5 Product data sheet ABR2S112B Performance Curves Electrical Durability of Contacts AC Loads Test conditions: in accordance with standard IEC 947-5-1 set up for rated control voltage. AC-12 operating cycles in millions AC-12 Control of resistive loads and isolated solid state loads via optocoupler (cos ϕ ≥ 0.9) (1) 24 V (2) 48 V (3) 115 V (4) 230 V AC-14 and AC-15 operating cycles in millions AC-14 Control of weak electro-magnetic loads of electro-magnets ≤ 72 VA (make: cos ϕ= 0.3, break: cos ϕ =0.3) AC-15 Control of electro-magnetic loads of electro-magnets > 72 VA (make: cos ϕ= 0.7, break: cos ϕ= 0.4) |
| Test conditions | in accordance with standard IEC 947-5-1 set up for rated control voltage. |
| DC | 12 operating cycles in millions |
| DC | 12 Control of resistive loads and isolated solid state loads via optocoupler (L/R ≤ 1 ms) |
| DC | 13 operating cycles in millions |
| DC | 13 Control of electro-magnets (L/R ≤ 2 x (Ue x Ie) in ms, with Ue: rated operating voltage and Ie: rated operating current, with a load protection diode |
Le système de contacts comprend un contact à fermeture unique, garantissant une commutation précise selon la norme CEI 947-5-1. La configuration sans contact à ouverture simplifie l'intégration dans les circuits de commande tout en maintenant une protection efficace.
La tension de circuit de commande offre une plage de fonctionnement étendue, allant de 250V à 277V, permettant une adaptation flexible aux différentes architectures électriques. Sa durée de vie mécanique exceptionnelle de 10 millions de cycles témoigne de sa robustesse.
Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 8 juin 2026. Source : https://seniadz.net/index.php/produit/abr2s112b/