En stock

INTERF R EM S175 BN 24VDC

Catégorie : Contrôle, Relais et Signalisation

Caractéristiques complémentaires

output interface module 9.5 mm -
electromechanical 24 V DC - 1 C/O low-level
[Ith] conventional free air thermal 0.05 A conforming to IEC 60947 1
Control circuit voltage limits 28.8 V energization threshold 16.9 V
Connections terminals Screw clamp terminal
Drop out voltage <= 3.8 V
[Ue] rated operational voltage <= 48 V AC conforming to IEC 60947 5-1
<= 48 V DC conforming to IEC 60947 5-1
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Operating time <= 6 ms between de energisation of coil and closing of NC contact
<= 6 ms between de energisation of coil and closing of NO contact DC
Contact bounce time <= 2 ms Operating rate in Hz 10 Hz at no load Mechanical durability >= 20000000 cycles
300 V conforming to IEC 60947 1
Installation category II conforming to IEC 60947 1
Standards IEC 60947 5-1
Fire resistance 960 °C conforming to IEC 60695 2-1
Shock resistance 30 gn for 11 ms conforming to IEC 60068 2-27
Vibration resistance 3 gn (f = 10...150 Hz) conforming to IEC 60068 2-6
Electromagnetic compatibility 1.2/50 µs shock waves immunity test, 0.5 kV for U < 50 V conforming to IEC 60947 1
1.2/50 µs shock waves immunity test, 1.5 kV for U < 150 V conforming to IEC 60947 1
1.2/50 µs shock waves immunity test, 2.5 kV for U < 300 V conforming to IEC 60947 1
61000 4-3
Electrostatic discharge immunity test level 3, 8 kV conforming to IEC 61000 4-2
Fast transients immunity test level 3, on input/output 1 kV conforming to IEC 61000 4-4
Fast transients immunity test level 3, on power supply 2 kV conforming to IEC 61000 4-4
Ambient air temperature for operation 5...40 °C unrestricted operation
Ambient air temperature for storage 40...80 °C
Pollution degree 2 conforming to IEC 60947 1