Génération du PDF…
Merci de patienter quelques secondes
d72b01012f88
Fiche technique · 31 mai 2026
| variable speed drive ATV32 | 3 kw - 400 V - 3 phase |
|---|---|
| [Us] rated supply voltage 380...500 V | 15...10 % |
| Supply frequency 50...60 Hz | 5...5 % |
| Speed range 1...100 asynchronous motor in open | loop mode |
| Speed accuracy +/ | 10 % of nominal slip 0.2 Tn to Tn |
| Torque accuracy +/ | 15 % |
| Flux vector control without sensor | Energy Saving, NoLoad law |
| Voltage/frequency ratio | Energy Saving, quadratic U/f |
| Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/ | 5 % <= 10 |
| mA overload and short | circuit protection |
| Bipolar differential voltage AI2 +/ | 10 V DC 30000 Ohm 10 bits |
| Current AI3 0...20 mA (or 4 | 20 mA, x-20 mA, 20-x mA or other patterns by |
| Response time 8 ms +/ | 0.7 ms LI1...LI6 logic |
| Accuracy +/ | 0.2 % AI1, AI2, AI3 for a temperature of -10...60 °C |
| +/ | 0.5 % AI1, AI2, AI3 for a temperature of 25 °C |
| +/ | 1 % AO1 for a temperature of 25 °C |
| +/ | 2 % AO1 for a temperature of -10...60 °C |
| Linearity error +/ | 0.2...0.5 % of maximum value AI1, AI2, AI3 |
| +/ | 0.3 % AO1 |
| Analogue output type Software | configurable current AO1 0...20 mA 800 Ohm 10 bits |
| Software | configurable voltage AO1 0...10 V 470 Ohm 10 bits |
| Switch | configurable PTC probe LI6 24...30 V DC |
| Short | circuit between motor phases drive |
| Physical interface 2 | wire RS 485 Modbus |
| Electromagnetic compatibility 1.2/50 µs | 8/20 µs surge immunity test level 3 IEC 61000-4-5 |
| Electrical fast transient/burst immunity test level 4 IEC 61000 | 4-4 |
| Electrostatic discharge immunity test level 3 IEC 61000 | 4-2 |
| Radiated radio | frequency electromagnetic field immunity test level 3 IEC 61000-4-3 |
| Conducted radio | frequency immunity test level 3 IEC 61000-4-6 |
| Voltage dips and interruptions immunity test IEC 61000 | 4-11 |
| EN 61800 | 3 environments 1 category C2 |
| EN 61800 | 3 environments 2 category C2 |
| EN/IEC 61800 | 3 |
| EN/IEC 61800 | 5-1 |
| C | Tick |
| pollution degree 2 EN/IEC 61800 | 5-1 |
| IP degree of protection IP20 EN/IEC 61800 | 5-1 |
| vibration resistance 1 gn 13...200 Hz EN/IEC 60068 | 2-6 |
| 1.5 mm peak to peak 3...13 Hz EN/IEC 60068 | 2-6 |
| shock resistance 15 gn 11 ms EN/IEC 60068 | 2-27 |
| relative humidity 5...95 % without condensation IEC 60068 | 2-3 |
| 5...95 % without dripping water IEC 60068 | 2-3 |
| ambient air temperature for operation | 10...50 °C without derating |
| ambient air temperature for storage | 25...70 °C |
| operating position Vertical +/ | 10 degree |
| RoHS (date code | YYWW) Compliant - since 1007 - Schneider Electric declaration of conformity |
| (2) Optional GV2 circuit | breaker |
| Option | Protection Device, GV2 circuit-breaker |
| The drive is prepared to be equipped with an optional GV2 circuit | breaker. |
| The GV2 circuit | breaker is directly mounted on the drive. Mechanical and electrical link are made using the optional adapter. The |
| NOTE | The product overall dimension, including GV2 adapter and EMC plate mounted, becomes 424 mm (16.7 in.) |
| (1) Ground screw (HS type 2 | 5x12) |
| Single or Three | phase Power Supply - Diagram with Line Contactor |
| Connection diagrams conforming to standards EN 954 | 1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in |
| accordance with standard IEC/EN 60204 | 1. |
| Single or Three | phase Power Supply - Diagram with Switch Disconnect |
| Connection diagrams conforming to standards EN 954 | 1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in |
| accordance with standard IEC/EN 60204 | 1. |
| Connection diagrams conforming to standards EN 954 | 1 category 3 and IEC/EN 61508 capacity SIL2, stopping category 0 in |
| accordance with standard IEC/EN 60204 | 1. |
| category 0 of standard IEC/EN 60204 | 1. |
| The STO safety function integrated into the product can be used to implement an "EMERGENCY STOP" (IEC 60204 | 1) for category 0 |
| Connection diagrams conforming to standards EN 954 | 1 category 2 and IEC/EN 61508 capacity SIL1, stopping category 0 in |
| accordance with standard IEC/EN 60204 | 1. |
| category 0 of standard IEC/EN 60204 | 1. |
| The STO safety function integrated into the product can be used to implement an "EMERGENCY STOP" (IEC 60204 | 1) for category 0 |
| Switch SW1 set to | |
| Switch SW1 set to | |
| Switch SW1 set to | |
| Switch SW1 set to |
Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 31 mai 2026. Source : https://seniadz.net/index.php/produit/atv32hu30n4/