b5c6590fd93e
Fiche technique du produit · 14 mai 2026
| circuit breaker Easypact EZC100B | TMD - 25 A - |
|---|---|
| [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947 | 2 |
| [Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Breaking capacity 10 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| 10 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| 5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| 2.5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| 7.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| 7.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| [Ics] rated service breaking capacity Ics 0.625 kA 550 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Ics 1.25 kA 440 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Ics 1.875 kA 380 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Ics 1.875 kA 400/415 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Ics 2.5 kA 110/130 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Ics 2.5 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Suitability for isolation Yes conforming to IEC 60947 | 2 |
| Trip unit name TM | D |
| Trip unit technology Thermal | magnetic |
| Disclaimer | This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications |
| Short | circuit protection |
| Pollution degree 3 conforming to IEC 60664 | 1 |
| 3 conforming to IEC 947 | 1 |
| Electrical durability Category A | 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Earth | leakage protection Without |
| IEC 60947 | 2 |
| JIS C8201 | 2-2 |
| Ambient air temperature for operation | 25...70 °C |
| Ambient air temperature for storage | 35...85 °C |
Clause de non-responsabilité : Cette fiche technique est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations pour des applications spécifiques sans validation technique préalable. Document généré le 14 mai 2026. Source : https://seniadz.net/index.php/produit/ezc100b3025/