EZC100N 15KA 4P3D 100A

Catégorie : Disjoncteurs forte puissance (boitier moulé et ouvert)

Complémentaires

circuit breaker Easypact EZC100N TMD - 100 A
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947 2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947 2
[Ue] rated operational voltage 250 V DC conforming to IEC 60947 2
550 V AC 50/60 Hz conforming to IEC 60947 2
Breaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947 2
25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947 2
25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947 2
5 kA Icu at 125 V DC 1P conforming to IEC 60947 2
5 kA Icu at 250 V DC 2P conforming to IEC 60947 2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947 2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947 2
18 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947 2
[Ics] rated service breaking capacity Ics 5 kA 440 V AC 50/60 Hz conforming to IEC 60947 2
Ics 9 kA 380...400 V AC 50/60 Hz conforming to IEC 60947 2
Ics 12.5 kA 110...130 V AC 50/60 Hz conforming to IEC 60947 2
Ics 12.5 kA 220...240 V AC 50/60 Hz conforming to IEC 60947 2
Ics 2.5 kA 125 V DC conforming to IEC 60947 2
Ics 2.5 kA 250 V DC conforming to IEC 60947 2
Ics 2.5 kA 550 V AC 50/60 Hz conforming to IEC 60947 2
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Ics 7.5 kA 415 V AC 50/60 Hz conforming to IEC 60947 2
Suitability for isolation Yes conforming to IEC 60947 2
Trip unit name TM D
Trip unit technology Thermal magnetic
Short circuit protection
Electrical durability Category A 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Earth leakage protection Without
Ambient air temperature for operation 25...70 °C
Ambient air temperature for storage 35...85 °C

Description

Clause de non-responsabilité : Cette fiche technique est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations pour des applications spécifiques sans validation technique préalable. Document généré le 15 mai 2026. Source : https://seniadz.net/index.php/produit/ezc100n4100/