Génération du PDF…

Merci de patienter quelques secondes

Fiche technique — 41bfe2bcca69 — EZC250H2250

EZC250H2250

41bfe2bcca69

Fiche technique · 29 mai 2026

EZC250H2250

EZC250H2250

41bfe2bcca69

En stock

MG EZC250 36KA 415V 2P 250A

Catégorie : Disjoncteurs forte puissance (boitier moulé et ouvert)

Caractéristiques complémentaires

circuit breaker Easypact EZC250H TMD - 250 A
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947 2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947 2
[Ue] rated operational voltage 250 V DC conforming to IEC 60947 2
550 V AC 50/60 Hz conforming to IEC 60947 2
Breaking capacity 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947 2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947 2
30 kA Icu at 125 V DC 1P conforming to IEC 60947 2
30 kA Icu at 250 V DC 2P conforming to IEC 60947 2
36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947 2
36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947 2
85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947 2
85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947 2
[Ics] rated service breaking capacity Ics 15 kA 125 V DC conforming to IEC 60947 2
Ics 15 kA 250 V DC conforming to IEC 60947 2
Ics 18 kA 380 V AC 50/60 Hz conforming to IEC 60947 2
Ics 18 kA 400/415 V AC 50/60 Hz conforming to IEC 60947 2
Ics 5 kA 550 V AC 50/60 Hz conforming to IEC 60947 2
Ics 12.5 kA 440 V AC 50/60 Hz conforming to IEC 60947 2
Ics 42.5 kA 110/130 V AC 50/60 Hz conforming to IEC 60947 2
Ics 42.5 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947 2
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Suitability for isolation Yes conforming to IEC 60947 2
Trip unit name TM D
Trip unit technology Thermal magnetic
Short circuit protection
Pollution degree 3 conforming to IEC 60664 1
3 conforming to IEC 947 1
Electrical durability Category A 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Earth leakage protection Without
IEC 60947 2
JIS C8201 2-2
Ambient air temperature for operation 25...70 °C
Ambient air temperature for storage 35...85 °C