3P CONTACTOR EasyPact TVS 1NO 4KW 400V

Catégorie : Contacteurs, sectionneurs, relais multifonctions

Caractéristiques complémentaires

EasyPact TVS contactor 3P(3 NO) AC-3 - <= 440
V 9A 110 V AC coil
Utilisation category AC 1
AC 3
[Ie] rated operational current 9 A (<= 60 °C) AC AC 3 for power circuit <= 440 V
25 A (<= 60 °C) AC AC 1 for power circuit <= 440 V
Irms rated making capacity 90 A 440 V AC for power circuit conforming to IEC 60947-4-1
[Icw] rated short time withstand current 105 kA at <= 40 °C - 10 s for power circuit
61 kA at <= 40 °C 60 s for power circuit
30 kA at <= 40 °C 600 s for power circuit
10 A gG <= 690 V type 1 control circuit IEC 60947 5-1
[Ui] rated insulation voltage 690 V conforming to IEC 60947 4-1
Electrical durability 1400000 cycles AC 3
150000 cycles AC 1
Power dissipation per pole 0.2 W AC 3
1.6 W AC 1
Standards IEC 60947 1
IEC 60947 4-1
IEC 60947 5-1
Connections terminals Power circuit : screw clamp terminals - 1 flexible cable(s) 1...4 mm² with cable end
Power circuit screw clamp terminals - 2 flexible cable(s) 1...2.5 mm² with cable end
Power circuit screw clamp terminals - 1 solid cable(s) 1...4 mm² without cable end
Power circuit screw clamp terminals - 2 solid cable(s) 1...4 mm² without cable end
Control circuit screw clamp terminals - 1 flexible cable(s) 1...4 mm² without cable
Control circuit screw clamp terminals - 2 flexible cable(s) 1...4 mm² without cable
Control circuit screw clamp terminals - 1 flexible cable(s) 1...4 mm² with cable end
Control circuit screw clamp terminals - 2 flexible cable(s) 1...2.5 mm² with cable end
Control circuit screw clamp terminals - 1 solid cable(s) 1...4 mm² without cable end
Control circuit screw clamp terminals - 2 solid cable(s) 1...4 mm² without cable end
0.3...0.6 Uc at <= 55 °C drop out 50 Hz Inrush power in VA 95 VA at 20 °C (0.75) 60 Hz 95 VA at 20 °C (0.75) 50 Hz Hold-in power consumption in VA 8.5 VA at 20 °C (0.3) 50 Hz 8.5 VA at 20 °C (0.3) 60 Hz Heat dissipation 2...3 W for control circuit Minimum switching current 5 mA control circuit Minimum switching voltage 17 V control circuit Non-overlap time 1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact Insulation resistance > 10 MOhm control circuit
ambient air temperature for storage 60...80 °C
permissible ambient air temperature around the device 20...70 °C at Uc
fire resistance 850 °C IEC 60695 2-1
RoHS (date code YYWW) Compliant - since 1110 - Schneider Electric declaration of conformity