Fiche technique — f92ee8a2d954 — LC3D09AE7

LC3D09AE7

f92ee8a2d954

Fiche technique du produit · 15 mai 2026

LC3D09AE7

LC3D09AE7

f92ee8a2d954

Commercialisé — En stock

S.D 1S ON PLATE 48V50/60 STAR DELTA

Catégorie : Contacteurs, sectionneurs, relais multifonctions

Complémentaires

TeSys D star delta starter - 3 x 3P (3 NO) - 9 A -
Utilisation category AC 3
Device presentation Pre wired
[Ie] rated operational current 9 A (<= 60 °C) AC AC 3 for power circuit at <= 440 V
[Ui] rated insulation voltage 690 V conforming to IEC 60947 4-1 power circuit
690 V conforming to IEC 60947 1 signalling circuit
Electrical durability 2 Mcycles 9 A AC 3 <= 440 V
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
IEC 60947 5-1
EN 60947 5-1
EN 60947 4-1
IEC 60947 4-1
Connections terminals Screw clamp terminals for power circuit 1 1...4 mm² flexible without cable end
Operating rate 30 cyc/h at <= 60 °C Starting time 30 s Coil technology Without built in suppressor module Control circuit voltage limits 0.3...0.6 Uc at 60 °C drop-out 50/60 Hz 0.8...1.1 Uc at 60 °C operational 50 Hz 0.85...1.1 Uc at 60 °C operational 60 Hz Inrush power in VA 70 VA at 20 °C 0.75 60 Hz 70 VA at 20 °C 0.75 50 Hz Hold-in power consumption in VA 7.5 VA at 20 °C 0.3 60 Hz 7 VA at 20 °C 0.3 50 Hz Heat dissipation 2...3 W at 50/60 Hz Auxiliary contacts type Mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC Mirror contact conforming to IEC 60947-4-1 3 x 1 NC Signalling circuit frequency 25...400 Hz Minimum switching current 5 mA for signalling circuit Switching voltage 17 V for signalling circuit Non-overlap time 1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact Width 143 mm Height 124 mm Depth 143 mm Product weight 1.53 kg Environment Insulation resistance > 10 MOhm for signalling circuit
Protective treatment TH conforming to IEC 60068 2-30
Ambient air temperature for storage 60...80 °C
Ambient air temperature for operation 40...70 °C at Uc
Fire resistance 850 °C conforming to IEC 60695 2-1
RoHS (date code YYWW) Compliant  - since  0845  -  Schneider Electric declaration of conformity
NOTE LC3 D09A to D18A: Mechanical interlock between KM3 and KM1.
Our Proposal Type 1 : Circuit Breaker + Contactor for Motor Power 7,5 kW and 415 VAC
Non contractual pictures. Type 1 coordination requires that in a short circuit condition, the contactor or starter must not present any danger to

Description

Clause de non-responsabilité : Cette fiche technique est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations pour des applications spécifiques sans validation technique préalable. Document généré le 15 mai 2026. Source : https://seniadz.net/index.php/produit/lc3d09ae7/