| 16...24 A | class 10A |
|---|---|
| one at 0 conforming to IEC 60947 | 4-1 |
| Overload tripping class Class 10A conforming to IEC 60947 | 4-1 |
| Tripping threshold 1.14 +/ | 0.06 Ir conforming to IEC 60947-4-1 |
| Mechanical robustness Shocks | 6 Gn for 11 ms conforming to IEC 60068-2-7 |
| Vibrations | 3 Gn conforming to IEC 60068-2-6 |
| [Ith] conventional free air thermal current Control circuit | 5 A |
| Associated fuse rating Control circuit | 5 A (gG) |
| Power circuit | 50 A (gG) |
| Power circuit | 25 A (aM) |
| [Ui] rated insulation voltage 690 V conforming to IEC 60947 | 4-1 |
| Control type Stop | red push-button |
| Reset | green push-button |
| Temperature compensation | 20...60 °C |
| Connections | terminals Screw clamp terminals (control circuit): 2 flexible cable(s) without cable end of 1...2.5 |
| Screw clamp terminals (control circuit) | 2 flexible cable(s) without cable end of 1...2.5 |
| Screw clamp terminals (control circuit) | 2 flexible cable(s) with cable end of 1...2.5 |
| Screw clamp terminals (control circuit) | 2 solid cable(s) without cable end of 1...2.5 |
| Screw clamp terminals (power circuit) | 1 flexible cable(s) without cable end of 2.5...10 |
| Screw clamp terminals (power circuit) | 1 flexible cable(s) with cable end of 1.5...6 |
| Screw clamp terminals (power circuit) | 1 solid cable(s) without cable end of 2.5...10 |
| Tightening torque Control circuit (screw clamp terminals) | 1.7 N.m |
| Control circuit (screw clamp terminals) | 1.7 N.m |
| Power circuit (screw clamp terminals) | 2.5 N.m |
| standards IEC 60947 | 4-1 |
| IEC 60947 | 5-1 |
| ambient air temperature for operation | 20...70 °C with derating |
| -20...60 °C without derating conforming to IEC 60947 | 4-1 |
| ambient air temperature for storage | 60...80 °C |
| fire resistance 850 °C conforming to IEC 60068 | 2-1 |
| dielectric strength 6 kV at 50 Hz conforming to IEC 60255 | 5 |
| electromagnetic compatibility Surge withstand | 6 kV conforming to IEC 60801-5 |
| RoHS (date code | YYWW) Compliant - since 1110 - Schneider Electric declaration of conformity |