Génération du PDF…

Merci de patienter quelques secondes

Fiche technique — c312f4d1c885 — LV429014

LV429014

c312f4d1c885

Fiche technique · 11 août 2026

LV429014

LV429014

c312f4d1c885

En stock

3P NSX100B WITHOUT TRIP UNIT COMPACT CI

Catégorie : Disjoncteurs forte puissance (boitier moulé et ouvert)

Caractéristiques complémentaires

circuit breaker Compact NSX100B 100 A - 3
poles without trip unit
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947 2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947 2
[Ue] rated operational voltage AC 50/60 Hz conforming to IEC 60947 2
Breaking capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947 2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947 2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947 2
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947 2
Suitability for isolation Yes conforming to EN 60947 2
Yes conforming to IEC 60947 2
Pollution degree 3 conforming to IEC 60947 1
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Mechanical durability 50000 cycles conforming to IEC 60947 2
Electrical durability 10000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947 2
20000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947 2
30000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947 2
50000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947 2
Standards EN 60947 2
IEC 60947 2
Ambient air temperature for operation 35...70 °C
Ambient air temperature for storage 55...85 °C
RoHS (date code YYWW) Compliant  - since  0819  -  Schneider Electric declaration of conformity

Description