a7094485ea4d
Fiche technique du produit · 15 mai 2026
| circuit breaker Compact NSX100B | TMD - 25 A - |
|---|---|
| [Ics] rated service breaking capacity Ics 20 kA 440 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Suitability for isolation Yes conforming to EN 60947 | 2 |
| Trip unit name TM | D |
| Trip unit technology Thermal | magnetic |
| Short | circuit protection (magnetic) |
| Pollution degree 3 conforming to IEC 60664 | 1 |
| Disclaimer | This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications |
| Electrical durability 10000 cycles 690 V In conforming to IEC 60947 | 2 |
| Long time pick | up adjstment type Ir Adjustable |
| Long time pick | up adjustment range 0.7...1 x In |
| [Tr] long | time delay adjustment 120...400 s 1.5 x In |
| Short | time pick-up adjustment type Isd Fixed |
| [Isd] short | time pick-up adjustment 300 A |
| Short | time delay adjustment type Fixed |
| Standards EN 60947 | 2 |
| IEC 60947 | 2 |
| Ambient air temperature for operation | 35...70 °C |
| Ambient air temperature for storage | 55...85 °C |
| RoHS (date code | YYWW) Compliant - since 0819 - Schneider Electric declaration of conformity |
Clause de non-responsabilité : Cette fiche technique est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations pour des applications spécifiques sans validation technique préalable. Document généré le 15 mai 2026. Source : https://seniadz.net/index.php/produit/lv429546/