4P3T TM32D VIGI MH NSX100B

Catégorie : Disjoncteurs forte puissance (boitier moulé et ouvert)

Caractéristiques complémentaires

circuit breaker VigiCompact TMD - Vigi MH
NSX100B 32A - 4 poles 3d
Breaking capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947 2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947 2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947 2
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947 2
[Ics] rated service breaking capacity Ics 20 kA 440 V AC 50/60 Hz conforming to IEC 60947 2
Ics 25 kA 380/415 V AC 50/60 Hz conforming to IEC 60947 2
Ics 40 kA 220/240 V AC 50/60 Hz conforming to IEC 60947 2
Ics 7.5 kA 500 V AC 50/60 Hz conforming to IEC 60947 2
Suitability for isolation Yes conforming to EN 60947 2
Yes conforming to IEC 60947 2
Trip unit name TM D
Trip unit technology Thermal magnetic
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Short circuit protection (magnetic)
Earth leakage add-on module name MH
Pollution degree 3 conforming to IEC 60664 1
Electrical durability 10000 cycles 690 V In conforming to IEC 60947 2
20000 cycles 690 V In/2 conforming to IEC 60947 2
30000 cycles 440 V In conforming to IEC 60947 2
50000 cycles 440 V In/2 conforming to IEC 60947 2
Long time pick up adjstment type Ir Adjustable
Long time pick up adjustment range 0.7...1 x In
[Tr] long time delay adjustment 15 s 6 x Ir
Short time pick-up adjustment type Isd Fixed
[Isd] short time pick-up adjustment 400 A
Short time delay adjustment type Fixed
Earth leakage protection class Class A
Earth leakage protection With
Residual earth leakage sensitity Adjustable 5 settings
[Δt] residual earth leakage sensitive 0.03...10 A
Residual earth leakage time delay Adjustable 4 settings
Standards EN 60947 2
IEC 60947 2
Ambient air temperature for operation 35...70 °C
Ambient air temperature for storage 55...85 °C
RoHS (date code YYWW) Compliant  - since  0839  -  Schneider Electric declaration of conformity

Description

Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 26 mai 2026. Source : https://seniadz.net/index.php/produit/lv429705/