317a6b5f7301
Fiche technique du produit · 15 mai 2026
| circuit breaker VigiCompact MH NSX160B | TMD |
|---|---|
| - 80 A | 3 poles 3d |
| [Ics] rated service breaking capacity Ics 20 kA 440 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Suitability for isolation Yes conforming to EN 60947 | 2 |
| Trip unit name TM | D |
| Trip unit technology Thermal | magnetic |
| Short | circuit protection (magnetic) |
| Earth | leakage add-on module name MH |
| Pollution degree 3 conforming to IEC 60664 | 1 |
| Disclaimer | This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications |
| Electrical durability 10000 cycles 440 V In/2 conforming to IEC 60947 | 2 |
| Long time pick | up adjstment type Ir Adjustable |
| Long time pick | up adjustment range 0.7...1 x In |
| [Tr] long | time delay adjustment 120...400 s 1.5 x In |
| Short | time pick-up adjustment type Isd Fixed |
| [Isd] short | time pick-up adjustment 640 A |
| Short | time delay adjustment type Fixed |
| Earth | leakage protection class Class A |
| Earth | leakage protection With |
| Residual earth | leakage sensitity Adjustable 5 settings |
| [Δt] residual earth | leakage sensitive 0.03...10 A |
| Residual earth | leakage time delay Adjustable 4 settings |
| Standards EN 60947 | 2 |
| IEC 60947 | 2 |
| Ambient air temperature for operation | 35...70 °C |
| Ambient air temperature for storage | 55...85 °C |
| RoHS (date code | YYWW) Compliant - since 0839 - Schneider Electric declaration of conformity |
Clause de non-responsabilité : Cette fiche technique est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations pour des applications spécifiques sans validation technique préalable. Document généré le 15 mai 2026. Source : https://seniadz.net/index.php/produit/lv430343/