4P4T MICROLOGIC 2.2 250A VIGI MH NSX250B

Catégorie : Disjoncteurs forte puissance (boitier moulé et ouvert)

Caractéristiques complémentaires

Micrologic 2.2 250 A - 4 poles 4d
Breaking capacity 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947 2
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947 2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947 2
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947 2
[Ics] rated service breaking capacity Ics 15 kA 500 V AC 50/60 Hz conforming to IEC 60947 2
Ics 20 kA 440 V AC 50/60 Hz conforming to IEC 60947 2
Ics 25 kA 380/415 V AC 50/60 Hz conforming to IEC 60947 2
Ics 40 kA 220/240 V AC 50/60 Hz conforming to IEC 60947 2
Suitability for isolation Yes conforming to EN 60947 2
Yes conforming to IEC 60947 2
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Protection type Instantaneous short circuit protection
Short time short circuit protection
Earth leakage add-on module name MH
Pollution degree 3 conforming to IEC 60664 1
Electrical durability 10000 cycles 440 V In conforming to IEC 60947 2
10000 cycles 690 V In/2 conforming to IEC 60947 2
20000 cycles 440 V In/2 conforming to IEC 60947 2
5000 cycles 690 V In conforming to IEC 60947 2
Long time pick up adjstment type Ir Adjustable 9 settings
Long time pick up adjustment range 0.9...1 x Io
[Tr] long time delay adjustment 11 s 7.2 x Ir
Short time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short time pick-up adjustment 1.5...10 x Ir
Short time delay adjustment type Fixed
Instantaneous pick up adjustment type Fixed
Instantaneous pick up adjustment 3000 A
Earth leakage protection class Class A
Earth leakage protection With
Residual earth leakage sensitity Adjustable 5 settings
[Δt] residual earth leakage sensitive 0.03...10 A
Residual earth leakage time delay Adjustable 4 settings
Standards EN 60947 2
IEC 60947 2
Ambient air temperature for operation 35...70 °C
Ambient air temperature for storage 55...85 °C
RoHS (date code YYWW) Compliant  - since  0839  -  Schneider Electric declaration of conformity