Génération du PDF…
Merci de patienter quelques secondes
f25023c018dd
Fiche technique · 11 août 2026
| Suitability for isolation Yes conforming to IEC 60947 | 2 |
|---|---|
| Trip unit rating 800 A ( | 5...70 °C) |
| [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947 | 2 |
| Disclaimer | This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications |
| [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Breaking capacity 50 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| [Ics] rated service breaking capacity 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947 | 2 |
| 10000 cycles (without maintenance) conforming to IEC 60947 | 2 |
| Electrical durability 6000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947 | 2 |
| 4000 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947 | 2 |
| [Icm] rated short | circuit making 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short | time withstand current 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
| 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947 | 2 |
| Instantaneous short | circuit protection |
| Short time short | circuit protection |
| Short | circuit |
| Long time pick | up adjstment type Ir Adjustable 9 settings |
| Long time pick | up adjustment range 0.4...1 x In |
| [Tr] long | time delay adjustment 0.5...24 s (6 x Ir) |
| Short | time pick-up adjustment type Isd Adjustable 9 settings |
| [Isd] short | time pick-up adjustment 1.5...10 x Ir |
| Short | time delay adjustment type Adjustable 5 settings |
| [Tsd] short | time delay adjustment 100...400 ms |
| Instantaneous pick | up adjustment type Adjustable 9 settings |
| Instantaneous pick | up adjustment 2...15 x In |
| Ground | fault pick-up adjustment type Adjustable 9 settings |
| Ground | fault time delay adjustment Adjustable 5 settings |
| type | tg |
| [Tg] ground | fault time delay 100...400 ms |
| [Ig] ground | fault pick-up adjustment 0.2...1 x In |
| Standards IEC 60947 | 2 |
| Pollution degree 4 conforming to IEC 60664 | 1 |
| Ambient air temperature for operation | 5...70 °C |
| Ambient air temperature for storage | 40...85 °C (without control unit) |
| RoHS (date code | YYWW) Compliant - since 1440 - Schneider Electric declaration of conformity |
Schneider Electric MVS08N3NW6V EasyPact MVS08 est un disjoncteur de 800A.
Il fournit une protection de base (LSIG), mais aussi un contrôle de l'énergie en temps opportun par comptage. Alors l'objet de cette version est de type débrochable à 3 pôles. Ce qui fait que le produit final est conforme à la norme IEC60947-2 et au niveau de pollution 4 selon IEC60664-1.
Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 11 août 2026. Source : https://seniadz.net/index.php/produit/mvs08n3mw6v/