EP MVS CB 3200A 50KA 4P MDO ETA5 DRAWOUT

Catégorie : Masterpact NT et NW

Complémentaires

Suitability for isolation Yes conforming to IEC 60947 2
Trip unit rating 3200 A ( 5...70 °C)
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947 2
Disclaimer This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947 2
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947 2
Breaking capacity 50 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947 2
[Ics] rated service breaking capacity 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947 2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947 2
10000 cycles (without maintenance) conforming to IEC 60947 2
Electrical durability 5000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947 2
2500 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947 2
[Icm] rated short circuit making 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short time withstand current 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947 2
25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947 2
Protection type Instantaneous short circuit protection
Short time short circuit protection
Short circuit
Long time pick up adjstment type Ir Adjustable 9 settings
Long time pick up adjustment range 0.4...1 x In
[Tr] long time delay adjustment 0.5...24 s (6 x Ir)
Short time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short time pick-up adjustment 1.5...10 x Ir
Short time delay adjustment type Adjustable 5 settings
[Tsd] short time delay adjustment 100...400 ms
Instantaneous pick up adjustment type Adjustable 9 settings
Instantaneous pick up adjustment 2...15 x In
Standards IEC 60947 2
Pollution degree 4 conforming to IEC 60664 1
Ambient air temperature for operation 5...70 °C
Ambient air temperature for storage 40...85 °C (without control unit)
RoHS (date code YYWW) Compliant  - since  1440  -  Schneider Electric declaration of conformity

Description

Clause de non-responsabilité : Cette fiche technique est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations pour des applications spécifiques sans validation technique préalable. Document généré le 16 mai 2026. Source : https://seniadz.net/index.php/produit/mvs32n4mw5a/