| asymmetrical flashing relay | 0.05..1 s - 24 V AC DC |
|---|---|
| Connections | terminals Screw terminals, clamping capacity: 2 x 1.5 mm² flexible with cable end |
| Screw terminals, clamping capacity | 2 x 2.5 mm² flexible without cable end |
| Setting accuracy of time delay +/ | 10 % of full scale |
| Repeat accuracy +/ | 0.2 % |
| [Ie] rated operational current <= 2 A DC | 13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 |
| <= 3 A AC | 15 at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 |
| <= 0.1 A DC | 13 250 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 |
| <= 0.2 A DC | 13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 |
| Input compatibility 3/4 wires sensors PNP/NPN without internal load, cable length | <= 50 m X1Z2 |
| 3/4 wires sensors PNP/NPN without internal load, cable length | <= 50 m X2Z2 |
| Potentiometer characteristic Linear 47 kOhm (+/ | 20 %), 0.2 W, cable length: <= 25 m Z1Z2terminal(s) Marking CE Overvoltage category III conforming to IEC 60664-1 [Ui] rated insulation voltage 250 V between contact circuit and control inputs IEC certified 250 V between contact circuit and power supply IEC certified 300 V between contact circuit and control inputs CSA certified 300 V between contact circuit and power supply CSA certified Supply disconnection value > 0.1 Uc |
| Surge withstand 2 kV conforming to IEC 61000 | 4-5 level 3 |
| Terminal description (15 | 16-18)OC_OFF |
| (B1 | A2)CO |
| standards EN/IEC 61812 | 1 |
| ambient air temperature for storage | 40...85 °C |
| ambient air temperature for operation | 20...60 °C |
| relative humidity 15...85 % (3K3) conforming to IEC 60721 | 3-3 |
| vibration resistance 0.35 mm (f = 10...55 Hz) conforming to IEC 60068 | 2-6 |
| shock resistance 15 gn for 11 ms conforming to IEC 60068 | 2-27 |
| pollution degree 3 conforming to IEC 60664 | 1 |
| non | dissipating shock wave 4.8 kV |
| resistance to electrostatic discharge 6 kV (in contact) conforming to IEC 61000 | 4-2 level 3 |
| 8 kV (in air) conforming to IEC 61000 | 4-2 level 3 |
| resistance to electromagnetic fields 10 V/m conforming to IEC 61000 | 4-3 level 3 |
| resistance to fast transients 2 kV conforming to IEC 61000 | 4-4 level 3 |
| disturbance radiated/conducted CISPR 11 group 1 | class A |
| CISPR 22 | class A |
| 2 12 | |
| 6 Start during the On | delay period: X2, Z2 linked.Start during the Off-delay period: X2, Z2 not linked. |
| Connection 3 | Wire NPN or PNP Sensor |
| Connection 3 | Wire NPN or PNP Sensor Without Using Terminal Z2 |
| 7 Off | delay adjustment (tr) (contact 15/16 closed). |
| 8 On | delay adjustment (ta) (contact 15/18 closed). |
| Example | An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and |
| necessary to apply a reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3 | k = 0.6 The electrical |
| durability therefore becomes | 1.5 10 operating cycles x 0.6 = 900 000 operating cycles. |
| Function L | Asymmetrical Flasher Relay (Starting Pulse Off) |
| Function | 1 Output |
| Function Li | Asymmetrical Flasher Relay (Starting Pulse On) |
| Function | 1 Output |
| Function Lt | Asymmetrical Flashing with Partial Stop of Timing |
| Function | 1 Output |
| Ta = t | |
| Relay de | energised |
| Ta | Adjustable On-delay |
| Tr | Adjustable Off-delay |