Génération du PDF…

Merci de patienter quelques secondes

Fiche technique — 815e22f35f57 — RE8TA11BUTQ

RE8TA11BUTQ

815e22f35f57

Fiche technique · 25 mai 2026

RE8TA11BUTQ

RE8TA11BUTQ

815e22f35f57

En stock

industrial timing relay - 0.1..10 s - type A - 24 V AC/DC, 110..240 V AC - 1 C/O

Catégorie : Schneider

Caractéristiques complémentaires

industrial timing relay 0.1..10 s - type A - 24 V
AC/DC, 110..240 V AC 1 C/O
Connections terminals Screw terminals 2 x 1.5 mm² , flexible cable with cable end
Setting accuracy of time delay +/ 20 % of full scale
[Ie] rated operational current <= 2 A at 24 V, DC 13 for 70 °C conforming to IEC 60947-5-1/1991
<= 2 A at 24 V, DC 13 for 70 °C conforming to VDE 0660
<= 3 A at 24 V, AC 15 for 70 °C conforming to IEC 60947-5-1/1991
<= 3 A at 24 V, AC 15 for 70 °C conforming to VDE 0660
<= 0.1 A at 250 V, DC 13 for 70 °C conforming to IEC 60947-5-1/1991
<= 0.1 A at 250 V, DC 13 for 70 °C conforming to VDE 0660
<= 0.2 A at 115 V, DC 13 for 70 °C conforming to IEC 60947-5-1/1991
<= 0.2 A at 115 V, DC 13 for 70 °C conforming to VDE 0660 Minimum switching capacity 10 mA at 12 V Marking CE Overvoltage category III conforming to IEC 60664-1 [Ui] rated insulation voltage 250 V conforming to IEC 300 V conforming to CSA Supply disconnection value > 0.1 Uc
Surge withstand 2 kV conforming to IEC 61000 4-5 level 3
Terminal description (15 16-18)OC_OFF
(A1 B1)CO
standards EN/IEC 61812 1
ambient air temperature for storage 40...85 °C
ambient air temperature for operation 20...60 °C
relative humidity 15...85 % 3K3 conforming to IEC 60721 3-3
vibration resistance 0.35 mm 10...55 Hz conforming to IEC 60068 2-6
pollution degree 3 conforming to IEC 60664 1
non dissipating shock wave 4.8 kV
resistance to electromagnetic fields 10 V/m conforming to IEC 61000 4-3 level 3
resistance to fast transients 2 kV conforming to IEC 61000 4-4 level 3
disturbance radiated/conducted CISPR 11 group 1 class A
CISPR 22 class A
Example An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and
necessary to apply a reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3 k = 0.6 The electrical
durability therefore becomes 1.5 10 operating cycles x 0.6 = 900 000 operating cycles.
Function A Power on Delay Relay
Function 1 Output
Function 2 Outputs
Relay de energised
Ta Adjustable On-delay
Tr Adjustable Off-delay

Description

Clause de non-responsabilité : Cette fiche est fournie à titre informatif. Senia Electrique ne saurait être tenu responsable de l'utilisation de ces informations sans validation technique préalable. Document généré le 25 mai 2026. Source : https://seniadz.net/index.php/produit/re8ta11butq/