MVS40N3NW6L

UGS : 95ff1a63354d Catégorie :

EP MVS CB 4000A 55kA 3P EDO 240VAC ET6 d

1.197.130,89DZD

UGS : 95ff1a63354d
Contenu
    Add a header to begin generating the table of contents
    Fiche technique du produit PDF :
    Référence : MVS40N3NW6L Marque : Schneider Disponibilité : En Stock

    Fiche Technique

    Télécharger
    • MVS40N3NW6L
    • Characteristics
    • EP MVS CB 4000A 55kA 3P EDO 240VAC ET6
    • drawout electrical circuit breaker
    • Main
    • Range of product EasyPact MVS
    • Range EasyPact
    • Product name MVS40N
    • Device short name MVS40N
    • Product or component type Circuit breaker
    • Device application Distribution
    • Poles description 3P
    • Protected poles description 3P 3d
    • Network type AC
    • Breaking capacity code N
    • Suitability for isolation Yes conforming to IEC 60947-2
    • Utilisation category Category B
    • Trip unit name ET6G
    • Trip unit technology Electronic
    • Trip unit rating 4000 A (-5...70 °C)
    • Complementary
    • Network frequency 50/60 Hz
    • Control type Electrically operated
    • Mounting mode Drawout
    • Mounting support Base plate
    • Rail
    • Connection position Horizontal
    • Vertical
    • Location of connection Rear
    • [In] rated current 4000 A (40 °C)
    • [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
    • [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
    • Jun 12, 2017
    • 1
    • Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
    • [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
    • Circuit breaker CT rating 4000 A
    • Breaking capacity 55 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
    • [Ics] rated service breaking capacity 55 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
    • Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
    • 10000 cycles (without maintenance) conforming to IEC 60947-2
    • Electrical durability 5000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2
    • 2500 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2
    • Connection pitch 115 mm (without spreader)
    • Contact position indicator Yes
    • [Icm] rated short-circuit making 121 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
    • capacity
    • [Icw] rated short-time withstand current 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
    • 55 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
    • 30 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
    • Trip unit protection functions LSIG
    • Protection type Earth fault
    • Instantaneous short-circuit protection
    • Overload protection (long time)
    • Short time short-circuit protection
    • Fault indication Overload
    • Short-circuit
    • Internal fault
    • Earth fault
    • Long time pick-up adjstment type Ir Adjustable 9 settings
    • Long time pick-up adjustment range 0.4...1 x In
    • Long time delay adjustment type Adjustable 9 settings
    • [Tr] long-time delay adjustment 0.5...24 s (6 x Ir)
    • Short-time pick-up adjustment type Isd Adjustable 9 settings
    • [Isd] short-time pick-up adjustment 1.5...10 x Ir
    • range
    • Short-time delay adjustment type Adjustable 5 settings
    • [Tsd] short-time delay adjustment 100...400 ms
    • range
    • Instantaneous pick-up adjustment type Adjustable 9 settings
    • Ii
    • Instantaneous pick-up adjustment 2...15 x In
    • range Off
    • Ground-fault pick-up adjustment type Adjustable 9 settings
    • Ground-fault time delay adjustment Adjustable 5 settings
    • type -tg
    • [Tg] ground-fault time delay 100...400 ms
    • adjustment range
    • [Ig] ground-fault pick-up adjustment 500...1200 A
    • range
    • Zone selective interlocking ZSI With
    • Current sensor rating range 1000/4000 A
    • Maximum breaking time 25 ms
    • Closing response time < 70 ms
    • Height 439 mm
    • Width 441 mm
    • Depth 395 mm
    • Product weight 90 kg
    • Environment
    • Standards IEC 60947-2
    • Product certifications CCC
    • GOST
    • IEC
    • 2
    • CCS
    • IP degree of protection IP40
    • Pollution degree 4 conforming to IEC 60664-1
    • Ambient air temperature for operation -5...70 °C
    • Ambient air temperature for storage -40...85 °C (without control unit)
    • -25...85 °C (with control unit)
    • Offer Sustainability
    • Sustainable offer status Green Premium product
    • RoHS (date code: YYWW) Compliant  - since  1440  -  Schneider Electric declaration of conformity
    • Schneider Electric declaration of conformity
    • REACh Reference not containing SVHC above the threshold
    • Reference not containing SVHC above the threshold
    • Product environmental profile Available
    • Product environmental
    • Product end of life instructions Available
    • End of life manual
    • Contractual warranty
    • Warranty period 18 months
    • 3

    Produits qui pourraient aussi répondre à vos besoins

    Produits récemment consultés

    OVA53000E

    19.270,58DZD

    KSB32CP11F

    23.327,15DZD

    MVS40N4NW2A

    1.840.269,25DZD

    références de produits

    100 000 de références

    Trouvez tout ce dont vous avez besoin dans notre catalogue

    livraison rapide

    Livraison adaptée à vos besoins

    Nos solutions de livraison fiables et rapides facilitent votre quotidien

    expert senia electrique

    Des conseils d’expert

    Recevez une assistance technique de spécialistes pour soutenir vos projets

    Panier
    Retour en haut