Référence : 18563
Marque : Schneider
Disponibilité : En Stock
- 18563
- Characteristics
- C120 - earth leakage add-on block - Vigi C120 - 2P -
- 125A - 30mA
- Main
- Product or component type Earth leakage add-on block
- Device short name Vigi C120
- Poles description 2P
- [In] rated current 125 A
- Network type AC
- Network frequency 50/60 Hz
- [Ue] rated operational voltage 230...415 V AC 50/60 Hz conforming to IEC 60947-
- 2
- Earth-leakage sensitivity 30 mA
- Earth-leakage protection time Instantaneous
- delay
- Earth-leakage protection class Class AC
- Standards EN 61009
- IEC 60947-2
- 9 mm pitches 7
- Complementary
- Device location in system Outgoer
- Residual current tripping technology Voltage independent
- [Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60947-2
- [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
- Mounting support 35 mm symmetrical DIN rail
- Electrical connection to mcb By screws
- Height 87 mm
- Width 117 mm
- Depth 73 mm
- Product weight 0.325 kg
- Colour Grey
- Mechanical durability 20000 cycles
- Connections - terminals Tunnel type terminals 1.5...50 mm² rigid
- Tunnel type terminals 1...35 mm² flexible
- Wire stripping length 15 mm
- Tightening torque 3.5 N.m
- Product compatibility Single terminal
- Environment
- IP degree of protection IP20
- pollution degree 3 conforming to IEC 60947-2
- electromagnetic compatibility 8/20 µs impulse withstand 250 A conforming to IEC 60947-2
- tropicalisation 2 conforming to EN 61009
- relative humidity 95 % ( 55 °C )
- operating altitude 2000 m
- ambient air temperature for operation -25...40 °C
- ambient air temperature for storage -40...70 °C
- 1 / 1
- The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
- This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.