[Ue] rated operational voltage 440 V AC conforming to EN/IEC 60947-2 50/60 Hz
Breaking capacity 36 kA Icu conforming to IEC 60947-2 at 440 V AC 50/60 Hz
36 kA Icu conforming to IEC 60947-2 at 380/415 V AC 50/60 Hz
70 kA Icu conforming to IEC 60947-2 at 220/240 V AC 50/60 Hz
Utilisation category Category A
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit rating 100 A ( 40 °C )
Protection type Overload protection (thermal)
Short-circuit protection (magnetic)
Complementary
Network frequency 50/60 Hz
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Jun 12, 2017
1
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Downside connection Front
Connections - terminals Screw connection
[Ui] rated insulation voltage 690 V conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
Thermal protection adjustment range 0...100 A
[Ics] rated service breaking capacity 18 kA conforming to IEC 60947-2 440 V AC 50/60 Hz
36 kA conforming to IEC 60947-2 380/415 V AC 50/60 Hz
70 kA conforming to IEC 60947-2 220/240 V AC 50/60 Hz
Mechanical durability 30000 cycles
Electrical durability 12000 cycles conforming to IEC 60947-2 415 V In
Connection pitch 35 mm
Contact position indicator Yes
Neutral protection setting No protection 3d
Long time pick-up adjstment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
Short-time delay adjustment type Fixed
Instantaneous pick-up adjustment type Fixed
Ii
Instantaneous pick-up adjustment 800 A
range
Height 161 mm
Width 140 mm
Depth 86 mm
Environment
Electrical shock protection class Class II
Standards IEC 60947-2
EN 60947-2
Product certifications GOST
IEC
IP degree of protection IP40
Pollution degree 3 conforming to IEC 60947-1
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1041 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold