UGS : fb55ab204641 Catégorie :
EP MVS CB 1600A 50KA 3P MDO ETV6 DRAWOUT

759.462,72DZD

UGS : fb55ab204641

Spécificités essentielles

Produits associés

Options et accessoires compatibles

Référence :

MVS16N3MW6V Marque : Schneider Disponibilité : En Stock



  • MVS16N3MW6V
  • Characteristics
  • EP MVS CB 1600A 50kA 3P MDO ETV6 drawout
  • manual Circuit breaker
  • Main
  • Range of product EasyPact MVS
  • Range EasyPact
  • Product name MVS16N
  • Device short name MVS16N
  • Product or component type Circuit breaker
  • Device application Distribution
  • Poles description 3P
  • Protected poles description 3P 3d
  • Network type AC
  • Breaking capacity code N
  • Suitability for isolation Yes conforming to IEC 60947-2
  • Utilisation category Category B
  • Trip unit name ETV6G
  • Trip unit technology Electronic
  • Trip unit rating 1600 A (-5...70 °C)
  • Complementary
  • Network frequency 50/60 Hz
  • Control type Manually operated
  • Mounting mode Drawout
  • Mounting support Base plate
  • Rail
  • Connection position Horizontal
  • Vertical
  • Location of connection Rear
  • [In] rated current 1600 A (40 °C)
  • [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
  • [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
  • Jun 12, 2017
  • 1
  • Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
  • [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
  • Circuit breaker CT rating 1600 A
  • Breaking capacity 50 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • [Ics] rated service breaking capacity 50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
  • 10000 cycles (without maintenance) conforming to IEC 60947-2
  • Electrical durability 6000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2
  • 4000 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2
  • Connection pitch 115 mm (without spreader)
  • Contact position indicator Yes
  • [Icm] rated short-circuit making 105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • capacity
  • [Icw] rated short-time withstand current 50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
  • 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
  • Trip unit protection functions LSIG
  • Protection type Earth fault
  • Instantaneous short-circuit protection
  • Overload protection (long time)
  • Short time short-circuit protection
  • Fault indication Overload
  • Short-circuit
  • Internal fault
  • Earth fault
  • Long time pick-up adjstment type Ir Adjustable 9 settings
  • Long time pick-up adjustment range 0.4...1 x In
  • Long time delay adjustment type Adjustable 9 settings
  • [Tr] long-time delay adjustment 0.5...24 s (6 x Ir)
  • Short-time pick-up adjustment type Isd Adjustable 9 settings
  • [Isd] short-time pick-up adjustment 1.5...10 x Ir
  • range
  • Short-time delay adjustment type Adjustable 5 settings
  • [Tsd] short-time delay adjustment 100...400 ms
  • range
  • Instantaneous pick-up adjustment type Adjustable 9 settings
  • Ii
  • Instantaneous pick-up adjustment 2...15 x In
  • range Off
  • Ground-fault pick-up adjustment type Adjustable 9 settings
  • Ground-fault time delay adjustment Adjustable 5 settings
  • type -tg
  • [Tg] ground-fault time delay 100...400 ms
  • adjustment range
  • [Ig] ground-fault pick-up adjustment 500...1200 A
  • range
  • Zone selective interlocking ZSI With
  • Display type Digital display
  • Type of measurement Voltage
  • Current sensor rating range 400/2000 A
  • Maximum breaking time 25 ms
  • Closing response time < 70 ms
  • Height 439 mm
  • Width 441 mm
  • Depth 395 mm
  • Product weight 70 kg
  • Environment
  • Standards IEC 60947-2
  • 2
  • Product certifications CCC
  • GOST
  • IEC
  • CCS
  • IP degree of protection IP40
  • Pollution degree 4 conforming to IEC 60664-1
  • Ambient air temperature for operation -5...70 °C
  • Ambient air temperature for storage -40...85 °C (without control unit)
  • -25...85 °C (with control unit)
  • Offer Sustainability
  • Sustainable offer status Green Premium product
  • RoHS (date code: YYWW) Compliant  - since  1440  -  Schneider Electric declaration of conformity
  • Schneider Electric declaration of conformity
  • REACh Reference not containing SVHC above the threshold
  • Reference not containing SVHC above the threshold
  • Product environmental profile Available
  • Product environmental
  • Product end of life instructions Available
  • End of life manual
  • Contractual warranty
  • Warranty period 18 months
  • 3

Produits Similaires

100 000 de références

Trouvez tout ce dont vous avez besoin dans notre catalogue

Livraison adaptée à vos besoins

Nos solutions de livraison fiables et rapides facilitent votre quotidien

Des conseils d’expert

Recevez une assistance technique de spécialistes pour soutenir vos projets

10
    10
    Votre panier
    BLRCH075A090B40
    BLRCH075A090B40
    1 X 9.586,77DZD = 9.586,77DZD
    ZB4BVB14
    ZB4BVB14
    1 X 1.075,10DZD = 1.075,10DZD
    140ACI04000
    140ACI04000
    1 X 263.693,15DZD = 263.693,15DZD
    XB6CF4B5B
    XB6CF4B5B
    1 X 2.374,86DZD = 2.374,86DZD
    LAEB1
    LAEB1
    1 X 1.431,45DZD = 1.431,45DZD
    schneider
    CA2KN22L7
    1 X 3.900,14DZD = 3.900,14DZD
    9001KN201F
    9001KN201F
    1 X 651,98DZD = 651,98DZD
    LD4LD030FC
    LD4LD030FC
    1 X 315.375,07DZD = 315.375,07DZD
    LC1D09Z7
    LC1D09Z7
    1 X 8.802,41DZD = 8.802,41DZD
    XPEM811
    XPEM811
    1 X 16.701,90DZD = 16.701,90DZD