Nos marques

Tous les produits Schneider

Produits récemment consultés

LV429318

4.628,42DZD

ISM11401

1.149,14DZD

ZC2JE015

19.085,94DZD

XALD102E

2.642,85DZD

MVS32H3NW5L

UGS : d386a590b39d Catégorie :
EP MVS CB 3200A 65KA 3P EDO 240VAC ET5 D

1.249.753,49DZD

UGS : d386a590b39d

Spécificités essentielles

Produits associés

Options et accessoires compatibles

Description du pruit
Référence :

MVS32H3NW5L Marque : Schneider Disponibilité : En Stock



  • MVS32H3NW5L
  • Characteristics
  • EP MVS CB 3200A 65kA 3P EDO 240VAC ET5
  • drawout electrical circuit breaker
  • Main
  • Range of product EasyPact MVS
  • Range EasyPact
  • Product name MVS32H
  • Device short name MVS32H
  • Product or component type Circuit breaker
  • Device application Distribution
  • Poles description 3P
  • Protected poles description 3P 3d
  • Network type AC
  • Breaking capacity code H
  • Suitability for isolation Yes conforming to IEC 60947-2
  • Utilisation category Category B
  • Trip unit name ET5S
  • Trip unit technology Electronic
  • Trip unit rating 3200 A (-5...70 °C)
  • Complementary
  • Network frequency 50/60 Hz
  • Control type Electrically operated
  • Mounting mode Drawout
  • Mounting support Base plate
  • Rail
  • Connection position Horizontal
  • Vertical
  • Location of connection Rear
  • [In] rated current 3200 A (40 °C)
  • [Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
  • [Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
  • Jun 12, 2017
  • 1
  • Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
  • [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
  • Circuit breaker CT rating 3200 A
  • Breaking capacity 65 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • [Ics] rated service breaking capacity 65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
  • Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
  • 10000 cycles (without maintenance) conforming to IEC 60947-2
  • Electrical durability 5000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2
  • 2500 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2
  • Connection pitch 115 mm (without spreader)
  • Contact position indicator Yes
  • [Icm] rated short-circuit making 143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • capacity
  • [Icw] rated short-time withstand current 65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
  • 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
  • Trip unit protection functions LSI
  • Protection type Instantaneous short-circuit protection
  • Overload protection (long time)
  • Short time short-circuit protection
  • Fault indication Overload
  • Short-circuit
  • Internal fault
  • Long time pick-up adjstment type Ir Adjustable 9 settings
  • Long time pick-up adjustment range 0.4...1 x In
  • Long time delay adjustment type Adjustable 9 settings
  • [Tr] long-time delay adjustment 0.5...24 s (6 x Ir)
  • Short-time pick-up adjustment type Isd Adjustable 9 settings
  • [Isd] short-time pick-up adjustment 1.5...10 x Ir
  • range
  • Short-time delay adjustment type Adjustable 5 settings
  • [Tsd] short-time delay adjustment 100...400 ms
  • range
  • Instantaneous pick-up adjustment type Adjustable 9 settings
  • Ii
  • Instantaneous pick-up adjustment 2...15 x In
  • range Off
  • Zone selective interlocking ZSI With
  • Current sensor rating range 1000/4000 A
  • Maximum breaking time 25 ms
  • Closing response time < 70 ms
  • Height 439 mm
  • Width 441 mm
  • Depth 395 mm
  • Product weight 90 kg
  • Environment
  • Standards IEC 60947-2
  • Product certifications CCC
  • GOST
  • IEC
  • CCS
  • IP degree of protection IP40
  • Pollution degree 4 conforming to IEC 60664-1
  • Ambient air temperature for operation -5...70 °C
  • Ambient air temperature for storage -40...85 °C (without control unit)
  • -25...85 °C (with control unit)
  • 2
  • Offer Sustainability
  • Sustainable offer status Not Green Premium product
  • RoHS (date code: YYWW) Will be compliant  on  2Q2016
  • Will be compliant  on  2Q2016
  • REACh Reference not containing SVHC above the threshold
  • Reference not containing SVHC above the threshold
  • Product environmental profile Available
  • Product end of life instructions Available
  • Contractual warranty
  • Warranty period 18 months
  • 3

Produits Similaires

100 000 de références

Trouvez tout ce dont vous avez besoin dans notre catalogue

Livraison adaptée à vos besoins

Nos solutions de livraison fiables et rapides facilitent votre quotidien

Des conseils d’expert

Recevez une assistance technique de spécialistes pour soutenir vos projets

10
    10
    Votre panier
    XC1AC146
    XC1AC146
    1 X 19.897,53DZD = 19.897,53DZD
    XC1AC141
    XC1AC141
    1 X 15.054,31DZD = 15.054,31DZD
    GB2CB09
    GB2CB09
    1 X 4.251,70DZD = 4.251,70DZD
    14882
    14882
    1 X 0,00DZD = 0,00DZD
    ALB45226
    ALB45226
    1 X 2.232,71DZD = 2.232,71DZD
    ALB45232
    ALB45232
    1 X 2.654,06DZD = 2.654,06DZD
    1 X 10.000,00DZD = 10.000,00DZD
    LRE12
    LRE12
    1 X 2.333,39DZD = 2.333,39DZD
    XZCP1440L5
    XZCP1440L5
    1 X 3.232,21DZD = 3.232,21DZD
    ISM10308
    ISM10308
    1 X 1.367,94DZD = 1.367,94DZD