Nos produits

MVS40N3NW2L

UGS : ef6bce483e1f Catégorie :

EP MVS CB 4000A 55kA 3P EDO 240VAC ET2 d

1.786.669,18DZD

Point de vente

  • Garantie de remboursement sans risque !
  • Remboursements sans tracas

Référence : MVS40N3NW2L
Marque : Schneider
Disponibilité : En Stock


Fiche Technique

Télécharger


Caractéristiques

MVS40N3NW2L
Characteristics
EP MVS CB 4000A 55kA 3P EDO 240VAC ET2
drawout electrical circuit breaker
Main
Range of product EasyPact MVS
Range EasyPact
Product name MVS40N
Device short name MVS40N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3P 3d
Network type AC
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ET2I
Trip unit technology Electronic
Trip unit rating 4000 A (-5…70 °C)
Complementary
Network frequency 50/60 Hz
Control type Electrically operated
Mounting mode Drawout
Mounting support Base plate
Rail
Connection position Horizontal
Vertical
Location of connection Rear
[In] rated current 4000 A (40 °C)
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
Jun 12, 2017
1
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit breaker CT rating 4000 A
Breaking capacity 55 kA (Icu) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 55 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability 5000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2
2500 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2
Connection pitch 115 mm (without spreader)
Contact position indicator Yes
[Icm] rated short-circuit making 121 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
capacity
[Icw] rated short-time withstand current 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
55 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LI
Protection type Instantaneous short-circuit protection
Overload protection (long time)
Fault indication Overload
Short-circuit
Internal fault
Long time pick-up adjstment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.4…1 x In
Long time delay adjustment type Adjustable 9 settings
[Tr] long-time delay adjustment 0.5…24 s (6 x Ir)
Thermal memory 20 minutes before and after tripping
Instantaneous pick-up adjustment type Adjustable 9 settings
Ii
Instantaneous pick-up adjustment 1.5…10 x Ir
range
Zone selective interlocking ZSI With
Current sensor rating range 1000/4000 A
Maximum breaking time 25 ms
Closing response time < 70 ms Height 439 mm Width 441 mm Depth 395 mm Product weight 90 kg Environment Standards IEC 60947-2 Product certifications CCC GOST IEC CCS IP degree of protection IP40 Pollution degree 4 conforming to IEC 60664-1 Ambient air temperature for operation -5...70 °C Ambient air temperature for storage -40...85 °C (without control unit) -25...85 °C (with control unit) Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant  - since  1440  -  Schneider Electric declaration of conformity Schneider Electric declaration of conformity REACh Reference not containing SVHC above the threshold 2 Reference not containing SVHC above the threshold Product environmental profile Available Product environmental Product end of life instructions Available End of life manual Contractual warranty Warranty period 18 months 3

Panier
MVS40N3NW2L
1.786.669,18DZD
Retour en haut